Appendix: Sound
S01.1 — Manage background noise level
Projects meet at least one of the following requirements to address background noise levels:
- An architectural drawing is provided that indicates the projected background noise level (dBA or NC) attributable to HVAC equipment noise, external noise intrusion or a similar source (e.g., a floor plan is color-coded to indicate dBA levels between regularly occupied spaces or across façade elements).
- A professional narrative is provided that indicates the measured background noise level (dBA or NC) attributable to HVAC equipment noise, external noise intrusion or a similar source in each space as denoted in Feature S02: Maximum Noise Levels.
S01.2 — Manage acoustical privacy
Projects meet at least one of the following requirements to address acoustical privacy:
- An architectural drawing is provided that indicates the projected acoustical performance of typical walls that separate regularly occupied spaces throughout the project (e.g., STC/Rw, NIC/Dw or equivalent sound transmission metrics denoted on a partition schedule from an architectural drawing set).
- A professional narrative is provided that indicates the measured level of acoustical privacy between regularly occupied spaces or within open workspace environments (e.g., NIC/Dw (or equivalent) or SPP data across partitions).
S01.3 — Label acoustic zones
The following zones are identified and labeled on the project floor plan:
- Loud zones: includes areas intended for appliances, mechanical equipment or amenities (e.g., kitchens, fitness rooms, social spaces, recreational rooms).
- Quiet zones: includes areas intended for focused work, wellness, rest, study and/or privacy.
- Mixed zones: includes areas intended for learning, collaboration and/or presentation.
S02.1 — Limit background noise levels
The following is achieved:
- Background noise levels do not exceed the thresholds below:
Sound Pressure Level (SPL) | Open Workspaces, Dining Areas | Enclosed Offices, Residential Living & Sleeping Areas (Daytime) | Conference Rooms, Classrooms, Residential Sleeping Areas (Nighttime) | Points | |
---|---|---|---|---|---|
Average SPL (Leq) | dBA | 45 | 40 | 35 | 3 |
dBC | 70 | 65 | 60 | ||
Max SPL (LMax) | dBA | 55 | 50 | 45 | |
dBC | 80 | 75 | 70 | ||
Average SPL (Leq) | dBA | 50 | 45 | 40 | 2 |
dBC | 75 | 70 | 65 | ||
Max SPL (LMax) | dBA | 60 | 55 | 50 | |
dBC | 85 | 80 | 75 | ||
Average SPL (Leq) | dBA | 55 | 50 | 45 | 1 |
dBC | 80 | 75 | 70 |
S03.1 — Ensure adequate wall construction
The following is achieved:
- In the spaces listed below, the sum of the background noise level (NC or NR) and sound insulation across a partition (NIC or Dw) meets the minimum SPP ratings listed in the table:
Source Room | Receiving Room | Minimum SPP |
---|---|---|
Enclosed Offices | Enclosed Offices | 75 |
Conference Rooms | 80 | |
Open Offices | 70 | |
Conference Rooms | Enclosed Offices | 85 |
Conference Rooms | 80 | |
Open Offices | 70 | |
Enclosed Quiet Zones (identified through S01: Sound Mapping, Part 3: Label Acoustic Zones) | 75 |
S03.2 — Ensure proper door specifications
Doors which connect private offices, conference rooms, classrooms and dwelling units to other spaces are constructed with two of the following requirements:
- Minimum STC-30 acoustical performance.
- Gaskets at the head and jambs.
- Automatic drop seal or sweep at base.
- A non-hollow core door.
S04.1 — Meet thresholds for reverberation time
The following is achieved:
- Spaces meet the maximum RT(60) thresholds in the table below:
Room Type | Size | RT(60) (seconds) |
---|---|---|
Conference Rooms | N/A | ≤ 0.6 |
Classrooms | < 280 m³ [10,000 ft³] | ≤ 0.6 |
Between 280 m³ [10,000 ft³] and 570m³ [20,000 ft³] | 0.5 to 0.8 | |
> 570 m³ [20,000 ft³] | 0.6 to 1.0 | |
Lecture Halls | < 280 m³ [10,000 ft³] | ≤ 0.7 |
Between 280 m³ [10,000 ft³] and 570m³ [20,000 ft³] | 0.6 to 0.9 | |
> 570 m³ [20,000 ft³] | 0.7 to 1.3 | |
Music rehearsal spaces | < 280 m³ [10,000 ft³] | ≤ 1.1 |
Between 280 m³ [10,000 ft³] and 570m³ [20,000 ft³] | 1.0 to 1.4 | |
Fitness facilities | < 280 m³ [10,000 ft³] | 0.7 to 0.8 |
Between 280 m³ [10,000 ft³] and 570m³ [20,000 ft³] | 0.8 to 1.1 | |
> 570 m³ [20,000 ft³] | 1.0 to 1.8 |
S04.2 — Implement sound reducing ceilings
Spaces have ceiling finishes that meet the following specifications:
- Ceiling treatment meets the minimum NRC/ αw values described below:
Space Type | NRC/ αw |
---|---|
Open Workspaces Enclosed Offices Dining Spaces |
0.7 for at least 75% of available ceiling area |
Conference Rooms Classrooms |
0.7 for at least 50% of available ceiling area |
S04.3 — Implement sound reducing vertical surfaces
Spaces have wall finishes that meet following requirement:
- Wall treatments meet the minimum NRC/αw values described below:
Space Type | NRC/ αw |
---|---|
Enclosed offices Dining spaces |
0.7 for at least 25% of at least one wall |
Conference rooms Classrooms |
0.7 for at least 25% of at least two walls |
S05.1 — Implement sound masking
Sound masking is provided in all of the following spaces and sound levels meet the following requirements when measured from the nearest workstation:
- Open offices, libraries, cafeterias, corridors/hallways: 45 - 48 dBA.
- Enclosed offices and quiet zones identified through S01: Sound Mapping, Part 3: Label Acoustic Zones: 40 - 42 dBA.